Vapor Permeance of Shower Wall Materials

A source-linked reference for contractors comparing the water-vapor permeance of shower membranes, tile backer boards, and common materials used in exterior shower-wall assemblies.

Document: REDTECH-02-090926Published: September 9, 2026Last fully verified: September 9, 2026Updated: September 10, 202617 product-specific entriesPrimary-source links includedASTM E96 methods preservedCurrent

Start here

Perm ratings are useful—but only when you know what was tested

A perm is a measure of water-vapor permeance: how readily water vapor passes through a specific material or product at a specific thickness under specified test conditions. Lower numbers mean greater resistance to vapor diffusion.

Do not treat this page as a lowest-number-wins ranking.

ASTM E96/E96M includes different test procedures and environmental conditions, and ASTM explicitly warns that a result obtained under one set of conditions cannot be used to predict the result under another. Thickness also matters. This resource therefore preserves the manufacturer-reported method, thickness, and threshold language wherever available.

For exterior shower walls, vapor control should be considered as part of the entire wall assembly—including climate, insulation, exterior sheathing, air control, drying direction, and the waterproofing layer immediately behind tile.

Reference classifications

How to read a perm rating

≤ 0.1 perm

Class I

Vapor impermeable / vapor barrier in the common building-science classification.

> 0.1 to ≤ 1

Class II

Vapor semi-impermeable; substantially slows diffusion while retaining more drying potential than Class I.

> 1 to ≤ 10

Class III

Vapor semi-permeable. Many conventional building materials fall in this range.

> 10 perms

Vapor permeable

Relatively open to water-vapor diffusion.

Classification thresholds follow Building Science Corporation's BSD-106 / Info-311 framework. Product suitability still depends on the complete assembly and application.

Master comparison

Manufacturer-published vapor permeance values for shower materials

This table prioritizes manufacturer technical data and retains the reported ASTM E96 method instead of normalizing unlike tests into a false ranking.

17 entries shown

Scroll horizontally to view all table columns.

Manufacturer-published vapor permeance data and reported test conditions
Product / materialCategoryThickness tested / reportedReported permeanceASTM E96 method / conditionsClassification*Source / notes
Wedi Vapor 85Foam backer board Complete assembly with specified seam / fastener treatment 0.03 permsASTM E96, Procedure EClass I Wedi 2026 Product Handbook
Wedi 2026 technical literature reports 0.03 perm for the Vapor 85 assembly with the specified seam and fastener treatment.
Wedi Subliner DrySheet membraneManufacturer system membrane0.05 permsASTM E96, Procedure EClass I Wedi 2026 Product Handbook
Corrected from the earlier 0.09 entry. Wedi technical literature reports an average permeance of approximately 0.051 perm.
ARDEX TLT™ Waterproofing MembraneSheet membrane5 mil0.051 permsASTM E96, Procedure E, 90% RHClass I ARDEX Americas
Manufacturer-published product value.
LATICRETE HYDRO BAN® Sheet MembraneSheet membraneNot stated on product page0.06 permsASTM E96/E96M, Procedure EClass I LATICRETE
Manufacturer-published product value.
NobleSeal® TSSheet membrane0.030 in.0.15 permsASTM E96/96M, Procedure E, 90% RHClass II Noble Company
Manufacturer-published product value.
Schluter®-KERDI-DSSheet membrane20 mil0.19 perms ASTM E96, desiccant / Procedure E, 90% RH Class II Schluter Systems
Schluter shower-system handbook reports 0.19 perms; some older pages report 0.18.
Mapelastic® AquaDefenseLiquid membraneAbout 20 mil dry minimum0.35 permsASTM E96, Method EClass II MAPEI
Current MAPEI product data reports 0.35 perms.
RedGard® Waterproofing and Crack Prevention Membrane Liquid membrane30 mil dry0.35 permsASTM E96, Method EClass II Custom Building Products
Value depends on cured film thickness; manufacturer reports 0.35 perms at 30 mil dry.
Schluter®-KERDI-BOARDFoam backer board1/2 in. (12.5 mm)0.36 perms ASTM E96, desiccant method, 100°F / 90% RH Class II Schluter Systems
Thickness-specific board value.
USG Durock™ Liquid Waterproofing and Crack Isolation Membrane Liquid membrane20 mil dry0.38 permsASTM E96, Procedure EClass II USG
Manufacturer-published product value.
Noble AquaSeal®Sheet membraneManufacturer sheet membrane< 0.5 permsASTM E96/96M, Procedure E, 90% RHClass II or better Noble Company
Threshold value, not an exact permeance.
Schluter®-KERDISheet membrane8 mil0.90 permsASTM E96, Procedure E, 90% RHClass II Schluter Systems
Manufacturer-published product value.
Johns Manville GoBoard®Foam backer boardCurrent listed board thicknesses< 1 perms ASTM E96; procedure not stated in data-sheet table Class II or better Johns Manville
Threshold value across the listed GoBoard thicknesses; not directly comparable to Procedure E values unless conditions match.
LATICRETE HYDRO BAN® liquid membraneLiquid membrane20–30 mil dry1.247 permsASTM E96-00e1, Procedure BClass III LATICRETE product data sheet
Different ASTM E96 procedure from most steam-shower Procedure E values; do not rank directly without noting test conditions.
Georgia-Pacific DensShield® Tile BackerFaced backer boardPanel alone< 1.5 perms ASTM E96; conditions not stated in cited submittal excerpt Exact class unresolved from <1.5 threshold Georgia-Pacific Gypsum
Manufacturer submittal reports less than 1.5 perms for panel alone and 1.0 perm with dry-set mortar.
PermaBASE® Cement BoardCement board1/2 in. and 5/8 in.> 10 permsASTM E96Vapor permeable PermaBASE / National Gypsum product data
Current product data reports greater than 10 perms for both listed thicknesses.
Wedi Building PanelFoam backer boardManufacturer board systemNot reported Water-vapor transmission listed as N/A in Wedi technical literature Not classified Wedi 2026 Product Handbook
Wedi technical literature lists water-vapor transmission as N/A. Waterproofness tests are reported separately; no numerical perm value is assigned here.

*Classification is assigned from the reported value using the reference thresholds above. Threshold values such as “<1” or “>10” are not exact measurements. The Class labels are for orientation, not a substitute for the manufacturer's application requirements.

Important comparability note

Most steam-shower membrane values in the table use ASTM E96 Procedure E / desiccant-type conditions, but not all do. For example, LATICRETE's published 1.247-perm HYDRO BAN liquid value is Procedure B. That number should not be interpreted as a head-to-head ranking against Procedure E values without accounting for the different test conditions.

Visual reference

Representative Procedure E / desiccant-type values on a logarithmic scale

This visual includes exact manufacturer-published values that are reasonably similar in test approach. Threshold-only entries, the Procedure B HYDRO BAN liquid result, and Wedi Building Panel are intentionally omitted.

Wedi Vapor 85
0.03 perm
Wedi Subliner Dry
0.05 perm
ARDEX TLT™ Waterproofing Membrane
0.051 perm
LATICRETE HYDRO BAN® Sheet Membrane
0.06 perm
NobleSeal® TS
0.15 perm
Schluter®-KERDI-DS
0.19 perm
Mapelastic® AquaDefense
0.35 perm
RedGard® Waterproofing and Crack Prevention Membrane
0.35 perm
Schluter®-KERDI-BOARD
0.36 perm
USG Durock™ Liquid Waterproofing and Crack Isolation Membrane
0.38 perm
Schluter®-KERDI
0.90 perm

Visual position is logarithmic because permeance values span orders of magnitude. It is a communication aid, not a substitute for the full test-method table.

Beyond the waterproofing layer

Common exterior-wall materials and vapor-control context

An exterior shower wall is an assembly. These reference entries help place the shower membrane or backer board in the context of framing-cavity and exterior-side materials.

Scroll horizontally to view all table columns.

Common wall-assembly materials and vapor-control context
MaterialCategoryThickness / contextVapor behaviorBasisClassificationSource note
Solid sheet steel (material reference)Solid metalAny practical sheet thickness Vapor-impermeable; steel permeability = 0 Material physics / building-science reference Vapor impermeable Building Science Corporation
Building Science Corporation states that the permeability of steel is zero. This is not an ASTM E96 product test.
6-mil polyethylene / sheet polyethyleneVapor-control layerTypical sheet Class I; ≤ 0.1 perm by classification Building-science classificationClass I Building Science Corporation
BSC identifies polyethylene as a Class I vapor retarder. Exact product values vary.
Kraft-faced fiberglass battInsulation facingAssembly-dependent Class II; > 0.1 to ≤ 1 perm by classification Building-science classificationClass II Building Science Corporation
BSC identifies kraft-faced fiberglass as a Class II vapor retarder.
Latex-painted gypsum boardInterior finish layerAssembly-dependent Class III; > 1 to ≤ 10 perms by classification Building-science classificationClass III Building Science Corporation
BSC uses latex-painted gypsum board as a Class III example.
1 in. extruded polystyrene (XPS)Rigid insulation1 in. or thicker≤ 1 permBuilding-science referenceClass II or lower Building Science Corporation
BSC notes that XPS at 1 inch or thicker has a perm value of 1.0 or less.
Plywood / OSB sheathingWood structural panelAssembly-dependent> 1 perm under wet-cup testingASTM E96 wet-cup contextClass III or more open Building Science Corporation
BSC notes plywood and OSB can exceed 1 perm in wet-cup testing; humidity sensitivity matters.
Non-perforated foil- or polypropylene-faced rigid insulation Faced rigid insulationProduct-dependent< 0.1 permBuilding-science referenceClass I Building Science Corporation
BSC identifies non-perforated foil and polypropylene-faced rigid insulations as below 0.1 perm.

Contractor interpretation

How to use this information on an exterior shower wall

1Identify the vapor-control layer behind the tile

Start with the actual waterproofing membrane or waterproof backer board, not the tile. Tile and grout are finish materials; the dedicated waterproofing/vapor-control layer is what should carry the moisture-management design intent.

2Check the exact test method and thickness

A 0.35-perm value at a specified dry-film thickness is not interchangeable with a board value at another thickness or a result obtained under another ASTM E96 procedure.

3Consider the exterior side of the wall

Low-permeance exterior insulation, foil facers, membranes, or other vapor-closed layers reduce outward drying. The interior shower-side layer therefore cannot be evaluated in isolation.

4Preserve a safe drying direction

Building Science Corporation cautions against “double vapor barriers” because assemblies need a practical drying path. A very low-perm shower-side layer can be appropriate, but the complete enclosure should be reviewed rather than stacking vapor-closed layers by habit.

5Separate vapor diffusion from air leakage

Perm ratings describe diffusion through materials. They do not measure air leakage through seams, electrical boxes, framing gaps, or penetrations. Air control and vapor control are related but different design functions.

6Treat solid metal differently from membranes

Building-science literature describes steel permeability as zero. A solid sheet-metal enclosure therefore does not provide a vapor-diffusion path through its body, but perimeter joints and transitions still have to be integrated into the surrounding wall's waterproofing and vapor-control strategy.

Exterior-wall caution

Lower permeance is not automatically better in every climate or assembly. Climate zone, indoor humidity, exterior insulation, sheathing, cladding, air conditioning, and available drying direction all matter. For unusual assemblies or high-risk projects, use a building-envelope professional rather than selecting materials from perm values alone.

Methodology

Why two “ASTM E96” numbers may still not be directly comparable

ASTM E96/E96M-24a is a gravimetric water-vapor-transmission standard with multiple test conditions. ASTM states that a result obtained in one method under one set of conditions cannot be used to predict the result under different conditions or another method.

  • Procedure matters. Dry-cup / desiccant conditions and wet-cup / water-method conditions can produce different results.
  • Relative humidity matters. Some materials become more vapor-open as humidity rises.
  • Temperature matters. Vapor pressure and material behavior change with test temperature.
  • Thickness matters. Product permeance is tied to the tested thickness; do not reuse a board or coating value at another thickness without manufacturer support.
  • Thresholds are not exact values. “<1 perm” may mean 0.95, 0.5, or far less. This resource never converts a threshold into a pretend exact measurement.

Scope and limitations

What this resource includes—and what it intentionally does not

Included: manufacturer-published permeance values for products commonly used in tiled showers, plus authoritative building-science references for common wall-assembly materials.

Not included as primary comparison values: isolated tile, grout, thinset, or sealant permeance. Those materials are highly installation-dependent and do not by themselves represent the continuity of the wall's intended waterproofing/vapor-control layer.

No value was inferred from marketing language. If a manufacturer says “low perm” but does not publish a numerical value in an accessible technical source, the product should not be assigned a number here until a source is located.

No endorsement is implied. A lower perm rating does not make one product universally superior; installation requirements, waterproofing performance, substrate compatibility, movement accommodation, service conditions, and system warranties remain separate considerations.

Why Redblock publishes this

A contractor resource first

Redblock Industries manufactures stainless-steel shower products, and publishes instructional articles on their website to help contractors and homeowners build better, safer showers. The purpose of this page is to make published vapor-permeance data easier to compare without stripping away the test conditions that give the numbers meaning.

The stainless steel material reference in the table above refers only to Redblock's own stainless shower niche, made from solid 1.2 mm 316L stainless-steel, a material considered to be vapor-impermeable according Building Science Corporation. This reference does not imply that sheet stainless steel products are used in any currently available shower wall waterproofing membrane system, as far as the publishers are aware.

See the Redblock Stainless Steel Shower Niche

Quick answers

Vapor permeance FAQ

Is a lower perm rating always better for a shower wall?

Yes, but the entire wall assembly and the exterior climate must be considered when deciding what materials should be used in the wall layers, and the order of these layers.

Is a waterproof shower membrane automatically a vapor barrier?

No. Waterproofing membranes are designed primarily to prevent liquid water migration, and vary drastically in their ability to manage water vapor transmission. Schluter notes that ANSI A118.10 is a liquid-water waterproofing standard and does not establish a universal vapor-permeance requirement.

Can I compare every ASTM E96 value directly?

No. ASTM E96 includes multiple methods and environmental conditions. Compare the procedure, RH, temperature, and tested thickness before treating two numbers as equivalent.

What perm rating is considered vapor-impermeable?

In the Building Science Corporation classification used on this page, 0.1 perm or less is vapor-impermeable / Class I.

Does cement board stop water vapor?

No. Even the most "waterproof" cement board available on the market is rated based on ANSI A118.10 which tests only liquid water penetration/ migration through the material. This standard does not involve any water vapor transmission testing.

Primary references

Core methodology and building-science sources

  1. ASTM E96/E96M-24a — Standard Test Methods for Gravimetric Determination of Water Vapor Transmission Rate of Materials
  2. Building Science Corporation — BSD-106: Understanding Vapor Barriers
  3. Building Science Corporation — Info-311: Vapor Open Assemblies
  4. Building Science Corporation — CP-1101: The Influence of Low-Permeance Vapor Barriers on Roof and Wall Performance
  5. Schluter Systems — Tiled Shower Waterproofing: note regarding water vapor

Every product row in the master table identifies its manufacturer source. Product data can change; Redblock should re-check manufacturer documents periodically and update the verification record only when that review has actually been completed.

Resource history

Verification and Revision Record

Meaningful content and verification changes to this Contractor Resource
DateVerification / revision
September 9, 2026 Initial publication with 15 product-specific entries and seven broader wall-assembly material references.
September 10, 2026 Added Wedi Vapor 85 and Wedi Building Panel; corrected Wedi Subliner Dry permeance from the earlier 0.09 entry to 0.05 perm (average approximately 0.051). The full dataset was not reverified on this date.